Up to 200°C, 1,5mm² IPL

 

Maximum Permissible Pipe Temp.°C
Output
(W/m)
IPL…C
IPL…CS
IPL…CF
 
6.5
190
190
190
13
180
185
185
23
150
160
160
33
110
115
115
50
75
80
75

 

 

 

 

Description

IPL is a constant wattage heating tape that can be used for freeze protection or maintenance of process temperatures in pipework and vessels. It can be cut-to-length at site and can replace mineral insulated (MI) cables for applications where the cut-to-length feature or field fabricated heating cable is preferred. IPL is approved for use in non-hazardous areas. Because of the special construction with “heating zones“ no additional cold lead is needed. From cut point to the next heating wire bonding point the heating cable remains cold and serves as cold lead. The installation of IPS heating tape is quick and simple and requires few special skills or tools. Termination and power connection components are all provided in convenient kits.

Technical data IPL

  • Power output: 6,5, 13, 23, 33, 50 W/m temperature independent
  • Outer sheath:  Silicone or Fluorpolymer
  • Maximum temperature switched on:  s. Tabelle
  • Maximum temperature switched off: 200°C
  • Minimum installation temperature:  –80°C (–112°F)
  • Voltage   220– 240VAC (other voltages.. see data sheet)
  • Maximum braiding resistance  <18,2 Ω/km